Standards Profile:
GB/T 17799.2-2023 is an electromagnetic compatibility EMC test standard, and applies to electronic products working in industrial environments EMC immunity test requirements specification. Below you can learn more about GB/T 17799.2-2023 test items, standard introduction, applicable test products and other related information. We also provide links to related EMC test instruments for reference.
Standard Name:
GB/T 17799.2-2023 General Standard for Electromagnetic Compatibility Part 2: Immunity Standards in Industrial Environments
Referenced in: IEC 61000-4-6:2016 standard.
GB/T 17799.2-2023 Which industrial products are applicable:
The purpose of GB/T 17799.2-2023 is to specify the immunity test requirements for continuous and transient, conducted and radiated disturbances and electrostatic discharges associated with electrical and electronic equipment used in industrial premises and directly connected to DC distribution grids or using batteries and used in industrial premises for which there is no dedicated product or product class immunity standard.
- The electromagnetic compatibility (EMC) immunity requirements of this document apply to the following electrical and electronic equipment used in industrial locations, covering the frequency range from 0 Hz to 400 GHz. Tests are not required at frequencies where immunity requirements are not specified.
- This general EMC immunity standard applies if there is no relevant specialized product or product class EMC immunity standard.
- This document applies to electrical and electronic equipment operating in industrial premises (as defined in 3.7), both indoor and outdoor This document also applies to equipment connected directly to a direct current (DC) distribution network or powered by batteries and used in industrial premises.
- This document specifies the immunity test requirements related to continuous and transient, conducted and radiated disturbances and electrostatic discharges for equipment within the scope of application.
Port definitions for industrial equipment:
GB/T 17799.2-2023 defines a variety of device ports, including AC power ports, DC power ports, signal ports, control ports, and enclosure ports.

GB/T 17799.2-2023 defines a variety of device ports
EMS test items of GB/T 17799.2-2023:
GB/T 17799.2-2023 defines different EMC immunity test requirements for each type of equipment port, for details, see the test specification test levels shown below and the contents of the relevant reference standards:
Enclosure port immunity test program for industrial equipment:
<<<<提醒:左右滑动表格>>>>serial number | EMS Test Program | test level | referenced standard | note | Performance Rating |
The following items are supplied by EUT TEST with test equipment and related accessories | |||||
1.1 | Industrial frequency magnetic field test instrument | 50 Hz, 30 A/m | IEC61000-4-8 | Only suitable for products containing products that are sensitive to magnetic fields | A |
1.2 | Radio Frequency Electromagnetic Field Test Instruments, Amplitude Modulation | 80-1000 MHz 10 V/m 80% AM modulation (1kHz) | IEC 61000-4-3 | RMS without modulation | A |
1.3 | Radio Frequency Electromagnetic Field Test Instruments, Amplitude Modulation | 1.4-6 GHz 3 V/m 80% AM modulation (1kHz) | IEC 61000-4-3 | RMS without modulation | A |
1.4 | Electrostatic Discharge Test Equipment | Contact discharge: ±4kV Air discharge: ±8kV | IEC 61000-4-2 | B |
Immunity test program for signal/control ports of industrial equipment:
<<<<提醒:左右滑动表格>>>>serial number | EMS Test Program | test level | referenced standard | note | Performance Rating |
The following items are supplied by EUT TEST with test equipment and related accessories | |||||
2.1 | RF Common Mode Immunity Tester | 0.15-80 MHz 10V 80%AM Modulation | IEC 61000-4-6 | RMS without modulation | A |
2.2 | Surge Immunity Tester Line-Ground | 1.2/50μS (8/20μS) ±1 kV | IEC 61000-4-5 | B | |
2.3 | Electrical fast transient pulse group immunity test requirements | ±1kV 5/50 ns 5/100kHz | IEC 61000-4-4 | Use of capacitive coupling clips | B |
Immunity test program for DC DC power input and output ports of industrial equipment:
<<<<提醒:左右滑动表格>>>>serial number | EMS Test Program | test level | referenced standard | note | Performance Rating |
The following items are supplied by EUT TEST with test equipment and related accessories | |||||
3.1 | RF Common Mode Immunity Tester | 0.15-80 MHz 10V 80%AM Modulation | IEC 61000-4-6 | RMS without modulation | A |
3.2 | Surge Immunity Tester Line-Ground Line - Line | 1.2/50μS (8/20μS) ±1 kV ±0.5 kV | IEC 61000-4-5 | B | |
3.3 | Electrical fast transient pulse group immunity test requirements | ±1kV 5/50 ns 5/100kHz | IEC 61000-4-4 | B |
Immunity test program for AC power input and output ports of industrial equipment:
<<<<提醒:左右滑动表格>>>>serial number | EMS Test Program | test level | referenced standard | note | Performance Rating |
The following items are supplied by EUT TEST with test equipment and related accessories | |||||
4.1 | RF Common Mode Immunity Tester | 0.15-80 MHz 10V 80%AM Modulation | IEC 61000-4-6 | RMS without modulation | A |
4.2 | Combined wave immunity test equipment Voltage Transient Droop Immunity Test Apparatus | 0%, 1 cycle 40% (10 cycles) - 70% (25 cycles) | IEC 61000-4-11 IEC 61000-4-34 | Voltage variation at zero crossing | B C |
4.3 | Voltage Interruption Test Equipment | 0%, 250 cycles | IEC 61000-4-11 IEC 61000-4-34 | Voltage variation at zero crossing | C |
4.4 | Surge Immunity Tester Line-Ground Line - Line | 1.2/50μS (8/20μS) ±2 kV ±1 kV | IEC 61000-4-5 | B | |
4.5 | Electrical fast transient pulse group immunity test requirements | ±2kV 5/50 ns 5/100kHz | IEC 61000-4-4 | B |
Future or specific industrial products need to be considered for testing immunity experiments and experimental levels:
<<<<提醒:左右滑动表格>>>>Test Item Name | referenced standard | Experimental grades in cited standards |
Ringing Wave Test | IEC61000-4-12 | 3 |
harmonic (wave with frequency an integer multiple of the fundamental) interharmonic wave | IEC 61000-4-13 | 3 |
Common mode conducted immunity below 150kHz | IEC 61000-4-16 | 3 |
Slow damped oscillatory wave | IEC61000-4-18 | 3 |
Below 150kHz Differential Mode Conducted Harassment | IEC 61000-4-19 | 4 |
DC power port voltage dips, interruptions and voltage variations testing | IEC 61000-4-29 | 2 |
Broadband Nuisance Test | IEC 61000-4-31 | await a decision |
and GB/T 17799.2-2023 related test standards:
- Immunity in residential, commercial and light industrial environments GB/T17799.1
- Part 2: Immunity standards for industrial environments GB/T17799.2
- Emissions in residential, commercial and light industrial environments GB17799.3
- Part 4: Emissions in the industrial environment GB17799.4
- Indoor equipment high altitude electromagnetic pulse (HEMP) immunity GB/T17799.5
- Immunity in power plant and substation environments GB/Z17799.6
- Part 7: Immunity requirements for equipment used to perform safety-related system functions (functional safety) in industrial locations GB/T 17799.7